LENZ LAW
AMENDMENT
AMENDMENT
.
This
amendment to fields 7 and 8 explains the handling of a
magnetic field by a ferromagnetic material, its relevancy
to Lenz Law and the most basic considerations when
attempting to build a prototype of a Lenz free generator.
I will
call ferromagnetic materials, which can't be appreciably
permanently magnetized "Soft Iron" (SI) in the
Leedskalnin's tradition for simplicity. Yet it includes
all ferromagnetic materials, be it plain mild steel or a
designer material such as the standard high silicone
steel used in transformer and generator laminations, or
high permeability dusts embedded in polymer.
As shown
in fields 7, these materials handle magnetic fields as if
they were conductors, rather than becoming temporary
magnets. The SI materials handle the magnetic field
somewhat similarly to the way any electric conductor
handles electric current.
A]
Magnetic field always finds the shortest path through the
SI material in order to close a magnetic loop.
B] There
are better and worse conductors of magnetic field and
there is only so much of a field (flux) an SI material
can handle, before it becomes saturated and refuse to
handle any more. Then the flux begins to bypass it
through the air.
C] SI
material can handle any direction and quantity of
polarities applied to it, as long as it does not become
saturated, but watch out what happens.
All of
these qualities (and quantities) are conditioned by the
ability of SI material to restructure its valence bond
geometries when it encounters magnetic field stronger
than the earth field.
Contrary
to electric conductors, there is no resistance, which
would heat up the SI material conducting a steady
magnetic field. Any heating up of ferromagnetic cores is
a result of wandering electric currents and eddy currents
when alternating the magnetic polarity in these
materials.
Please
note that these schematics show only the way the magnetic
field tends to tie into loop(s). Saturations as well as
the ratios of shapes and sizes of all the involved parts
are the factors, which eventually decide the final field
shapes and relationships.
Fig 1
When we
look at the electric induction in standard commercial
alternators, we may realize that the open core coil
arrangement forces the induced magnetic field of a coil
to exit the coil core and find its return path around the
coil back into the core as well as through the excitation
core material. While doing so, both cores handle the
inducing field as well as the induced fields in either
combination of opposing polarities, or a combination of
shared polarity. Permanent magnets used for excitation of
coils may do the same to a lesser degree, depending on
arrangements and their unspent permeability.
Figure 2
shows the polarities in opposition while the inducing
field fingers are approaching the coil cores and the
reason why the rotor of a commercial generator realizes
back torque while approaching the coil cores. While this
is happening, the inducing field is forced to break
through, and/or intermingle with the induced coil field
across the gap in order to actually keep inducing any
current in the induction coil at all, as it approaches
it. The coil core has to handle both flux orientations at
the same time and the degree of its saturation
corresponds to the sum of the strength of both fields.
(Probably a bit more.)
I have
depicted the core materials in purple in order to
represent their handling of both polarities. The color
coded arrows represent the orientations of magnetic flux
polarities. Note that the diagram is applicable only to
this particular way of winding.
Fig 2
Figure 3
shows the shared polarity and field, while the inducing
field finger is receding from the coil core. This is the
reason why the rotor of a generator also realizes back
torque while its fingers recede from the coil cores. The
inducing field becomes shared with the with the induced
coil field across the gap during the recession and
attracts to it. The finger as well as the coil core has
to handle only single polarity shared field and the
degree of its saturation corresponds more or less only to
the strength of the induction field. (Probably slightly
more.)
I have
used standard North and South coloring on the core
materials. The color coded arrows again show the
orientation of the polarities. Note that the diagram is
applicable only to this particular way of winding.
Fig 3
Of
course, the strength of magnetic field of the stator
coils under el. current increases with the Ampere value,
which is the strength of the load current. This means,
that the more current circulates through the induction
windings of a generator, the stronger is the force
between the induction field and the induced field, be it
attractive, or repulsive. This strength is expressed in
the theoretical (math) work of Lenz and called Lenz Law
also called back torque.
This
effect can be easily circumvented by either allowing the
induced field to close upon itself within a closed core
(a transformer like core), as you may see in Fields 8 -
Fig 1, or by offering it to close across a gap again, but
where it does not affect the inducing field, as you can
see in Fields 8 - Fig 2 .
The
closed core, or a core open anywhere but where the
induced field may interact with the inducing field in
air, does not handle anything which is not handled by the
contemporary commercial generator design open cores. It
only handles the same in a more sensible manner.
All of
an open core flux will cross an air gap at its narrowest,
as long as the narrowest has enough unsaturated SI
material to conduct it. See figure 4.
Fig 4
If the
material of the narrowest, or nearest gap becomes
saturated, the flux may split into two, or more localized
external fields depending on the order of the gap
material saturations. See figures 5a and 5b.
Fig 5a
Fig 5b
Further,
any ferromagnetic material placed into the gap will serve
as conductor and only the remaining sum of now two gaps
become the actual gap width. In other words, if you place
1" long piece of SI material into a 2" gap, the
actual gap counts is only as 1", even though the
material may not be in contact with the core.
It is
imperative to design with enough material at the point of
air gap to lead all the magnetic field flux across only
there. This means that a garage kind of an experimenter
better over design on the quantity of the SI material,
rather than risk loosing what may account for a
substantial portion of the flux where it is useless.
It makes
also sense to be generous and keep distance between any
SI parts at least twice as far apart compared to the
width of an intended air gap where the field should cross
over.
Another
aspect of electric induction is reluctance of the core
material. This particular phenomenon addresses the
resistance of SI materials to alternately re-polarize. It
is not likely to affect this kind of power generation
experimental results at standard RPM, lets say 3600 RPM
or less, even if you use regular structural mild steel.
I have
bounced this principle of a typical expert. Here is the
gist of it.
[Expert]
It will
not work because the fields clashing within the closed
core will hinder the induction. You will not get the
power output you get with the standard equipment.
[Me]
a)
Hardly. Once contained within the core, the core material
structure below saturation will handle the flux of both
fields without any problem thanks to its ferromagnetic
properties.
b) The
fields would have to be clashing within the standard
cores as well, yet it does not appear that the induction
is hindered. If it is, there is no reason to expect it to
get any worse with the closed cores than what you get
with the standard open cores. Considering that
contemporary generators get as high as 90% efficiency
between the shaft input and the el. power output, your
argument is not sound.
c) The
stated contemporary generator efficiency shows that 90%
of the back torque in them is due to Lenz effect, the
rest belonging to the excitation coil(s) resistance
losses, friction and magnetic drag.
[Expert]
Yes,
contemporary generators are already up to 90% efficient.
How can you possibly make them remarkably more efficient?
[Me]
The
generator efficiency is calculated between the shaft
input and the electric power output. Steam turbine inputs
1000 Kw turning the shaft and you get 900 Kw in electric
power out of the generator. This efficiency calculation
approach does not take into consideration that you may
need only lets say 100 Kw at the shaft in order to get
your 900 Kw at the coils. This would be exactly the case
if Lenz effect was eliminated and the generator was built
as efficient as the contemporary generators, all effects
(friction, excitation circuit losses, geometries etc.)
considered.
[Expert]
But that
is impossible. It violates the Law of Energy
conservation.
[Me]
No, it
is illegal within the classic understanding of Newton's
Law of Energy Conservation. This understanding does not
take into consideration that closed systems mentioned in
its formulation are only theoretical constructs designed
to ignore what the physicist considers unimportant. No
one has ever built and demonstrated a closed system yet.
A closed system would have to exclude everything,
including the gravitational field. If you are interested
here is one wrong
Newton's Law, just to show you
that laws are breakable.
[Expert]
You are
a crackpot.
Fields
10 make me look like a cheff of all cooks.
No hay comentarios:
Publicar un comentario